Thursday, 19 September 2013

Electrical Tools

Excel base Programs (Electrical Engineering):Designed by: Jignesh.Parmar

(1) Cable size and Voltage Drop Calculation

  FREE DOWNLOAD          BUY UNLOCK VERSION
  • Calculate Voltage drop of Cable.
  • Calculate  Size of Cable as per Electrical Load.
  • Calculate Current Capacity of Cable.
  • Calculate No of Run of Cable.
  • Calculate Motor Starting Voltage Drop.
  • Calculate Motor Running Voltage Drop.
  • Select appropriate Starter for Motor.

(2) Conduit Size Selection Program

      FREE DOWNLOAD          BUY UNLOCK VERSION
  • Calculate Size of Conduit for LT Cable/CAT-5 Cable/Fiber Optical Cable.

(3) Selection of  MCCB, ELCB  For Main /Branch Circuit.

      FREE DOWNLOAD            BUY UNLOCK VERSION
  • Calculate  Size and Type of Main MCCB/RCCB/ELCB for Continuous and Non Continuous Load
  • Calculate  Sensitivity of MCCB/RCCB/ELCB.
  • Calculate Size of  Cable.
  • Calculate Size and Type of Sub Circuit MCCB/MCB for Continuous and Non Continuous Load
  • Calculate Total Load .
  • Calculate Main and Branch Circuit Current.

(4) Selection of Fuse

  • Calculate Size of Fuse for Electrical Circuit.

(5) Size of Capacitor  For Power Factor Improvements

    FREE DOWNLOAD               BUY UNLOCK VERSION
  • Calculate Active and Reactive Power of System.
  • Calculate Leading Kvar of system.
  • Calculate Kvar/Phase.
  • Calculate Size of Capacitor for Power Factor Improvements.
  • Calculate Size of Main Fuse of Capacitor Bank
  • Calculate Size of Main Circuit Breaker
  • Calculate Thermal/Magnetic Setting of Circuit Breaker.
  • Calculate Max.Demand/KVA Demand/Total Annual cost befor Power Factor Correction.
  • Calculate Max.Demand/KVA Demand/Total Annual cost After Power Factor Correction.
  • Calculate Annual Saving by improving Power Factor by Capacitor.
  • Design Capacitor bank according to it’s Step Combination.

(6) Short Circuit Current Calculation at Various Point of Electrical Circuits(Isc).

     FREE DOWNLOAD                BUY UNLOCK VERSION
  • Calculate Short Circuit Current  at Substation.
  • Calculate Short Circuit Current at Distribution point.
  • Calculate Short Circuit Current at Transformer.
  • Calculate Short Circuit Current at Main Panel.
  • Calculate Short Circuit Current at Sub Distribution Board.

(7) Circuit Breaker Tripping Settings.

  • Calculate  Tripping Setting of Circuit Breaker.

(8) Motor Specifications

  • Calculate Various Specification of Motor.

(9) Calculate  Home Electrical Load & Electrical Bill.

         FREE DOWNLOAD               BUY UNLOCK VERSION
  • Calculate Electrical Bill of Home
  • Calculate Size of MCCB/MCB for Domestic Load
  • Calculate Electrical Load of Home.

(10) Calculate Insulation Resistance Value and PI value

    FREE DOWNLOAD.          BUY UNLOCK VERSION
  • Calculate minimum Insulation Resistance Value for Various Electrical Equipments.
  • Calculate IR Value of Electrical Equipments.
  • Graph of  IR Value
  • Calculate Polarization Index Value with Graph
  • Calculate Earth Resistivity.

(11) Calculate Electrical Load and Energy Consumption of Panel.

        FREE DOWNLOAD.         BUY UNLOCK VERSION
  • Calculate Continuous and non Continuous Electrical Load of Panel.
  • Calculate total Energy Consumption(KWH) in Daily/Monthly of Panel.
  • Calculate Size of MCB of each branch circuit of Panel.
  • Calculate Voltage / Voltage Difference of Each Phase
  • Calculate Unbalanced Load in Neutral Wire.
  • Calculate Expected Temperature rise in Each Phase.
  • Calculate Load in Each Phase.
  • Calculate Starting/Full Load/Continuous/Non Continuous Load
  • Calculate Size/Type/Tripping setting of Main MCCB.

(12) Calculate Electrical Load of Panel.

    FREE DOWNLOAD.           BUY UNLOCK VERSION
  • Calculate Voltage / Voltage Difference of Each Phase
  • Calculate Unbalanced Load in Neutral Wire.
  • Calculate Expected Temperature rise in Each Phase.
  • Calculate Load in Each Phase and Outgoing Feeders.
  • Calculate Starting/Full Load/Continuous/Non Continuous Load
  • Calculate Size of Cables for Each Outgoing Feeder.

(13) Calculate Size of Battery Bank and Inverter.

    FREE DOWNLOAD         BUY UNLOCK VERSION
  • Calculate Total Demand Load
  • Calculate Size of Battery Bank in Amp.Hr.
  • Select Type of Connection of Batteries in Battery Bank
  • Select Rating of Each Battery in Battery Bank
  • Calculate Size of Inverter.
  • Calculate Size/Type/Tripping setting of Main MCCB.

(14) Calculate Size of Solar Panel / Battery Bank / Inverter.

   FREE DOWNLOAD            BUY UNLOCK VERSION
  • Calculate Total Demand Load
  • Calculate Size of Solar Panel.
  • Select Type of Connection of Solar Panel.
  • Select Rating of Each Solar Panel.
  • Calculate Energy from Solar Panel as per Daily Sun lights.
  • Calculate Size Battery Bank.
  • Select Type of connection of Batteries in Battery Bank
  • Calculate size of Inverter

(15) Calculate No of Lighting Fittings and Lumen Output.

    FREE DOWNLOAD         BUY UNLOCK VERSION
  • Calculate Total Lumen Output for particular Area.
  • Calculate Total No of Lighting Lamps.
  • Calculate Total No of Lighting Fixtures.
  • Calculate No of Fittings along with the Length and Width of Room.

(16) Calculate Bus Bar Size and Voltage Drop.

  • Calculate Voltage Drop for  Bus Bar.
  • Select Size of Bus Bar for particular Load.
  • Enter Your Sub Panel Details like Load,Line Length.

(17) Design of Earthing Mat for Sub-Station:

      FREE DOWNLOAD      BUY UNLOCK VERSION
  • Program is design as per ANSI/IEEE 80-1986 Code.
  • Calculate Step Potential of Switch yard.
  • Calculate Touch Potential of Switch yard.
  • Calculate Total Length of Earthing Mat Conductor.
  • Calculate Size of Earthing Mat Conductor.
  • Calculate Total No of Earthing Rods.

(18) Calculate Touch Voltage and Ground Current.

      FREE DOWNLOAD              BUY UNLOCK VERSION
  • Calculate Resistance of Each Phase.
  • Calculate  Resistance of neutral/Ground.
  • Calculate Neutral Current and Load.
  • Calculate Touch Voltage for Metal part to Earth.
  • Calculate Body Resistance and Body Current.

(19) Calculate Size of Diesel Generator.

     FREE DOWNLOAD                 BUY UNLOCK VERSION
  • Calculate Size of D.G Set for Linear,Non-Linear Load
  • Calculate Size of D.G Set for Motor Load
  • Calculate D.G Set Efficiency.
  • Calculate UPL (Unit per Liter) of D.G Set
  • Calculate Unit Power Cost of D.G Set
  • Calculate Approximate Fuel Consumption.

(20) Calculate Size of air conditioning for room.

      FREE DOWNLOAD.                BUY UNLOCK VERSION
  • Calculate Size of Air Conditioning for Your Room.
  • Calculate AC Size in BTU/Hr.
  • Calculate AC size in Tone.
  • Calculate Heating and Cooling BTU.

(21) Calculate Transverse Load on PCC/RCC/RSJ/Tublar/RSJ Pole..

  FREE DOWNLOAD.      
  • Calculate Crippling load on Pole
  • Calculate Wind Load on Pole.
  • Calculate wind Load on all Conductors.
  • Calculate Transverse Load on Pole
  • Decide spacing between Two Conductor as per IS:5613.
  • Calculate required Voltage level of Overhead Line according to Distance.

(22) Calculate % Voltage Regulation of Small Distribution Line.

  • Calculate % Voltage Regulation of Small Distribution Line
  • Calculate % Voltage drop of Individual Load.
  • Calculate % Voltage drop of Various ACSR, AAAC, AAC conductor overhead Line.
  • Calculate Receiving end Voltage of Distribution Line.
  • Calculate Total % Voltage Regulation of Distribution Line.

(23) IDMT Over current & Earth Fault Relay Setting:

     FREE DOWNLOAD              BUY UNLOCK VERSION
  • Calculate IDMT Over Current Relay Setting (50/51)
  • Calculate IDMT Over Current Relay Pick up setting.
  • Calculate IDMT Over Current Relay PSM.
  • Calculate IDMT Over Current Relay Time setting.
  • Calculate Actual Operating time according to Various IES Curve.
  • Calculate Low current Setting(I>).
  • Calculate High Current Setting(I>>)
  • Calculate Actual Operating Time of Relay(t>)
  • Calculate Actual Operating Time of Relay(t>>)
  • Calculate IDMT Earth Fault Relay Setting (50N/51N) 
  •  Calculate IDMT Earth Fault Relay Pick up setting.
  • Calculate IDMT Earth Fault Relay PSM
  • Calculate IDMT Earth Fault Relay Time setting
  • Calculate Actual Operating time according to Various IES Curve.
  • Calculate Low current Setting(Ie>)
  • Calculate High Current Setting(Ie>>)
  •  Calculate Actual Operating Time of Relay(te>)
  •  Calculate Actual Operating Time of Relay(te>>)

(24) IDMT Relay Setting & Curves:

       FREE DOWNLOAD     BUY UNLOCK VERSION
  • Calculation of Actual Plug (Relay Pick up) setting of Various IDMT Relay.
  • Calculate PSM of Various IDMT Relay.
  • Calculate Time setting of Various IDMT Relay.
  • Calculate Total Grading Time of Various IDMT Relay.
  • Calculate Actual Operating time according to Various IES Curve.
  • Draw Various IDMT Relay characteristic Curve.

(25) IDMT Over Current Relay Grading Calculation (50/51):

    FREE DOWNLOAD.             BUY UNLOCK VERSION
  • Calculate IDMT Over current Relay Grading up to 5 Nos of Radial Bus bar System.
  • Calculate Relay Pick up setting of IDMT Over current Relay from Downstream to Source End.
  • Calculate PSM of Various IDMT Relay from Downstream to Source End.
  • Calculate Time setting of Various IDMT Relay from Downstream to Source End.
  • Calculate Total Grading Time of Various IDMT Relay from Downstream to Source End.
  • Calculate Actual Relay Operating time according to Various IES Curve.

(26) Transformer IDMT Over Current & Earth Fault Relay Setting:

    FREE DOWNLOAD        BUY UNLOCK VERSION
  • Calculate LT & HT Side IDMT Over Current Relay Setting (50/51)
  • Calculate LT & HT Side IDMT Over Current Relay Pick up setting.
  • Calculate LT & HT Side IDMT Over Current Relay PSM.
  • Calculate LT & HT Side IDMT Over Current Relay Time setting.
  • Calculate Actual Operating time according to Various IES Curve.
  • Calculate LT & HT Side Low current Setting(I>).
  • Calculate LT & HT Side High Current Setting(I>>)
  • Calculate LT & HT Side Actual Operating Time of Relay(t>)
  • Calculate LT & HT Side Actual Operating Time of Relay(t>>)
  • Calculate LT & HT Side IDMT Earth Fault Relay Setting (50N/51N) 
  •  Calculate LT & HT Side IDMT Earth Fault Relay Pick up setting.
  • Calculate LT & HT Side IDMT Earth Fault Relay PSM
  • Calculate LT & HT Side IDMT Earth Fault Relay Time setting
  • Calculate Actual Operating time according to Various IES Curve.
  • Calculate LT & HT Side Low current Setting(Ie>)
  • Calculate LT & HT Side High Current Setting(Ie>>)
  •  Calculate LT & HT Side Actual Operating Time of Relay(te>)
  •  Calculate LT & HT Side Actual Operating Time of Relay(te>>)
  • Calculate Differential Protection Relay setting:
  • Calculate Percentage Differential Current at Normal tapping
  • Calculate Percentage Differential Current at Highest tapping
  • Calculate Percentage Differential Current at Lowest tapping

(27) Calculate Transformer Over current Protection (As per NEC 450.3)

     FREE DOWNLOAD.            BUY UNLOCK VERSION
  • Calculate Size of Circuit Breaker on Primary side of Transformer as per NEC 450.3
  • Calculate Size of Fuse on Primary side of Transformer as per NEC 450.3
  • Calculate Size of Circuit Breaker on Secondary side of Transformer as per NEC 450.3
  • Calculate Size of Fuse on Secondary side of Transformer as per NEC 450.3
  • Calculate Size of Transformer
  • Calculate Transformer Full Load Losses.

(28) Calculate Number of Plate / Pipe Earthing:

      FREE DOWNLOAD     BUY UNLOCK VERSION
  • Calculate Permissible Current Density of Earth Electrode (Id).
  • Calculate No of Copper Plates Earthing Required .
  • Calculate No of Pipe Earthing Required.
  • Calculate Overall Earthing Resistance of Earthing Electrodes.
  • Calculate Resistance of Earthing Strip/Wire.
  • Calculate Resistance as per Arrangement of Plate/Pipe Earthing.
  • Calculate Total Earth Resistance of Plate/Pipe Earthing & Earth Strip.
  • Calculate Minimum Size of of Earth Strip.

(29) Calculate Motor-Pump Size:

    FREE DOWNLOAD          BUY UNLOCK VERSION
  • Calculate Pump Hydraulic Power
  • Calculate Motor-Pump Shaft Power
  • Calculate Pump Size.
  • Calculate Motor Size.
(30) Design DOL/Star-Delta Starter:
  • Calculate Lock Rotor Current.
  • Calculate Motor Starting Current.
  • Calculate Motor Full Load Current.
  • Calculate Non-time Delay/Time Delay fuse Size.
  • Calculate Circuit Breaker Size.
  • Calculate Overload Relay setting.
  • Calculate Type of Contactor.
  • Calculate Size of Main Contactor.
  • Calculate Size of Star Contactor.
  • Calculate Size of Delta Contactor.
  • Standard Arrangement of Main and Auxiliary Contactor.
(31) Size of Transformer and Voltage drop due to starting of large Motor
  • Calculate Lock Rotor Current.
  • Calculate Motor Starting Current.
  • Calculate Motor Full Load Current.
  • Calculate Non-time Delay/Time Delay fuse Size.
  • Calculate Circuit Breaker Size.
  • Calculate Overload Relay setting.
  • Calculate Type of Contactor.
  • Calculate Size of Main Contactor.
  • Calculate Size of Star Contactor.
  • Calculate Size of Delta Contactor.
  • Standard Arrangement of Main and Auxiliary Contactor

(32) Calculate Number of Lighting Fixtures & Lux Level

    FREE DOWNLOAD         BUY UNLOCK VERSION
  • Calculate required No of Fixtures.
  • Calculate required No of Lamps.
  • Calculate Watts / Sq.foot.
  • Calculate Energy Cost / Year.
  • Calculate Actual Lux Level.

Impact of Floating Neutral in Power Distribution

Introduction:

  • If The Neutral Conductor opens, Break or Loose at either its source side (Distribution Transformer, Generator or at Load side (Distribution Panel of Consumer), the distribution system’s neutral conductor will “float” or lose its reference ground Point. The floating neutral condition can cause voltages to float to a maximum of its Phase volts RMS relative to ground, subjecting to its unbalancing load Condition.
  •  Floating Neutral conditions in the power network have different impact depending on the type of Supply, Type of installation and Load balancing in the Distribution. Broken Neutral or Loose Neutral would damage to the connected Load or Create hazardous Touch Voltage at equipment body. Here We are trying to understand the Floating Neutral Condition in T-T distribution System.

What is Floating Neutral?

  • If the Star Point of Unbalanced Load is not joined to the Star Point of its  Power Source (Distribution Transformer or Generator) then Phase voltage do not remain same across each phase but its vary according to the Unbalanced of the load.
  • As the Potential of such an isolated Star Point or Neutral Point is always changing and not fixed so it’s called Floating Neutral.

Normal Power Condition & Floating Neutral Condition

             Normal Power Condition:

  • On 3-phase systems there is a tendency for the star-point and Phases to want to ‘balance out’ based on the ratio of leakage on each Phase to Earth. The star-point will remain close to 0V depending on the distribution of the load and subsequent leakage (higher load on a phase usually means higher leakage).
  • Three phase systems may or may not have a neutral wire. A neutral wire allows the three phase system to use a higher voltage while still supporting lower voltage single phase appliances. In high voltage distribution situations it is common not to have a neutral wire as the loads can simply be connected between phases (phase-phase connection).
  • 3 Phase 3 Wire System:
  • Three phases has properties that make it very desirable in electric power systems. Firstly the phase currents tend to cancel one another (summing to zero in the case of a linear balanced load). This makes it possible to eliminate the neutral conductor on some lines. Secondly power transfer into a linear balanced load is constant.
  • 3 Phase 4 Wire System for Mix Load:
  • Most domestic loads are single phase. Generally three phase power either does not enter domestic houses or it is split out at the main distribution board.
  • Kirchhoff’s Current Law states that the signed sum of the currents entering a node is zero. If the neutral point is the node, then, in a balanced system, one phase matches the other two phases, resulting in no current through neutral. Any imbalance of Load will result in a current flow on neutral, so that the sum of zero is maintained.
  • For instance, in a balanced system, current entering the neutral node from one Phase side is considered positive, and the current entering (actually leaving) the neutral node from the other side is considered negative.
  • This gets more complicated in three phase power, because now we have to consider phase angle, but the concept is exactly the same. If we are connected in Star connection with a neutral, then the neutral conductor will have zero current on it only if the three phases have the same current on each. If we do vector analysis on this, adding up sin(x), sin(x+120), and sin(x+240), we get zero.
  • The same thing happens when we are delta connected, without a neutral, but then the imbalance occurs out in the distribution system, beyond the service transformers, because the distribution system is generally a Star Connected.
  • The neutral should never be connected to a ground except at the point at the service where the neutral is initially grounded (At Distribution Transformer). This can set up the ground as a path for current to travel back to the service. Any break in the ground path would then expose a voltage potential. Grounding the neutral in a 3 phase system helps stabilize phase voltages. A non-grounded neutral is sometimes referred to as a “floating neutral” and has a few limited applications.

          Floating Neutral Condition:

  • Power flows in and out of customers’ premises from the distribution network, entering via the Phase and leaving via the neutral. If there is a break in the neutral return path electricity may then travel by a different path. Power flow entering in one Phase returns through remaining two phases. Neutral Point is not at ground Level but it Float up to Line Voltage. This situation can be very dangerous and customers may suffer serious electric shocks if they touch something where electricity is present.
  • Broken neutrals can be difficult to detect and in some instances may not be easily identified. Sometimes broken neutrals can be indicated by flickering lights or tingling taps. If you have flickering lights or tingly taps in your home, you may be at risk of serious injury or even death.

Voltage Measurement between Neutral to Ground:

  • A rule-of-thumb used by many in the industry is that Neutral to ground voltage of 2V or less at the receptacle is okay, while a few volts or more indicates overloading; 5V is seen as the upper limit.
  • Low Reading: If Neutral to ground voltage is low at the receptacle than system is healthy, If It is high, then you still have to determine if the problem is mainly at the branch circuit level, or mainly at the panel level.
  • Neutral to ground voltage exists because of the IR drop of the current traveling through the neutral back to the Neutral to ground bond. If the system is correctly wired, there should be no Neutral to Ground bond except at the source transformer (at what the NEC calls the source of the Separately Derived System, or SDS, which is usually a transformer). Under this situation, the ground conductor should have virtually no current and therefore no IR drop on it. In effect, the ground wire is available as a long test lead back to the Neutral to ground bond.
  • High Reading: A high reading could indicate a shared branch neutral, i.e., a neutral shared between more than one branch circuits. This shared neutral simply increases the opportunities for overloading as well as for one circuit to affect another.
  • Zero Reading: A certain amount of Neutral to ground voltage is normal in a loaded circuit. If the reading is stable at close to 0V. There is a suspect an illegal Neutral to ground bond in the receptacle (often due to lose strands of the neutral touching some ground point) or at the subpanel. Any Neutral to ground bonds other than those at the transformer source (and/or main panel) should be removed to prevent return currents flowing through the ground conductors.

Various Factors which cause Neutral Floating:

  • There are several factors which are identifying as the cause of neutral floating. The impact of Floating Neutral is depend on the position where Neutral is broken
1)    At The Three Phase Distribution Transformer:
  • Neutral failure at transformer is mostly failure of Neutral bushing.
  • The use of Line Tap on transformer bushing is identified as the main cause of Neutral conductor failure at transformer bushing. The Nut on Line Tap gets loose with time due to vibration and temperature difference resulting in hot connection. The conductor start melting and resulting broke off Neutral.
  • Poor workmanship of Installation and technical staff also one of the reasons of Neutral Failure.
  • A broken Neutral on Three phases Transformer will cause the voltage float up to line voltage depending upon the load balancing of the system. This type of Neutral Floating may damage the customer equipment connected to the Supply.
  • Under normal condition current flow from Phase to Load to Load to back to the source (Distribution Transformer). When Neutral is broken current from Red Phase will go back to Blue or Yellow phase resulting Line to Line voltage between Loads.
  • Some customer will experience over voltage while some will experience Low voltage.
2)    Broken Overhead Neutral conductor in LV Line:
  • The impact of broken overhead Neutral conductor at LV overhead distribution will be similar to the broken at transformer.
  • Supply voltage floating up to Line voltage instead of phase Voltage. This type of fault condition may damage customer equipment connected to the supply.
3)    Broken of Service Neutral Conductor:
  • A broken Neutral of service conductor will only result of loss of supply at the customer point. No any damages to customer equipments.
4)    High Earthing Resistance of Neutral at Distribution Transformer:
  • Good Earthing Resistance of Earth Pit of Neutral provide low resistance path for neutral current to drain in earth. High Earthing Resistance may provide high resistance Path for grounding of Neutral at Distribution Transformer.
  • Limit earth resistance sufficiently low to permit adequate fault current for the operation of protective devices in time and to reduce neutral shifting.
5)    Over Loading & Load Unbalancing:
  • Distribution Network Overloading combined with poor load distribution is one of the most reason of Neutral failure.
  • Neutral should be properly designed so that minimum current will be flow in to neutral conductor. Theoretically the current flow in the Neutral is supposed to be zero because of cancellation due to 120 degree phase displacement of phase current.
  • IN= IR<0 + IY<120 + IB<-120.
  • In Overloaded Unbalancing Network lot of current will flow in Neutral which break Neutral at its weakest Point.
6)    Shared neutrals
  • Some buildings are wired so that two or three phases share a single neutral. The original idea was to duplicate on the branch circuit level the four wire (three phases and a neutral) wiring of panel boards. Theoretically, only the unbalanced current will return on the neutral. This allows one neutral to do the work for three phases. This wiring shortcut quickly became a dead-end with the growth of single-phase non-linear loads. The problem is that zero sequence current
  • From nonlinear loads, primarily third harmonic, will add up arithmetically and return on the neutral. In addition to being a potential safety problem because of overheating of an undersized neutral, the extra neutral current creates a higher Neutral to ground voltage. This Neutral to ground voltage subtracts from the Line to Neutral voltage available to the load. If you’re starting to feel that shared neutrals are one of the worst ideas that ever got translated to copper.
7)    Poor workmanship & Maintenance :
  • Normally LV network are mostly not given attention by the Maintenance Staff. Loose or inadequate tightening of Neutral conductor will effect on continuity of Neutral which may cause floating of Neutral.

 How to detect Floating Neutral Condition in Panel:

  • Let us Take one Example to understand Neutral Floating Condition.We have a Transformer which Secondary is star connected, Phase to neutral = 240V and Phase to phase = 440V.
    Condition (1): Neutral is not Floating
  • Whether the Neutral is grounded the voltages remain the same 240V between phase & Neutral and 440V between phases. The Neutral is not Floating.
 Condition (2): Neutral is  Floating
  • All Appliances are connected: If the Neutral wire for a circuit becomes disconnected from the household’s main power supply panel while the Phase wire for the circuit still remains connected to the panel and the circuit has appliances plugged into the socket outlets. In that situation, if you put a voltage Tester with a neon lamp onto the Neutral wire it will glow just as if it was Live, because it is being fed with a very small current coming from the Phase supply via the plugged-in appliance(s) to the Neutral wire.
  • All Appliances are Disconnected: If you unplug all appliances, lights and whatever else may be connected to the circuit, the Neutral will no longer seem to be Live because there is no longer any path from it to the Phase supply.
  • Phase to Phase Voltage: The meter indicates 440V AC. (No any Effect on 3 Phase Load)
  • Phase to Neutral Voltage: The meter indicates 110V AC to 330V AC.
  • Neutral to Ground Voltage: The meter indicates 110V.
  • Phase to Ground Voltage: The meter indicates 120V.
  • This is because the neutral is “floats” above ground potential (110V + 120V = 230VAC). As a result the output is isolated from system ground and the full output of 230V is referenced between line and neutral with no ground connection.
  • If suddenly disconnect the Neutral from the transformer Neutral but kept the loading circuits as they are, Then Load side Neutral becomes Floating since the equipment that are connected between Phase to Neutral will become between Phase to Phase ( R to Y,Y to B), and since they are not of the same ratings, the artificial resulting neutral will be floating, such that the voltages present at the different equipments will no longer be 240V but somewhere between 0 (not exactly) and the 440 V (also not exactly). Meaning that on one line Phase to Phase, some will have less than 240V and some will have higher up to near 415. All depends on the impedance of each connected item.
  • In an unbalance system, if the neutral is disconnected from the source, the neutral becomes floating neutral and it is shifted to a position so that it is closer to the phase with higher loads and away from the phase with smaller load. Let us assume an unbalance 3 phase system has 3 KW load in R-phase, 2 KW load in Y-phase and 1 KW load in B-phase. If the neutral of this system is disconnected from the main, the floating neutral will be closer to R-phase and away from B-phase. So, the loads with B-phase will experience more voltage than usual, while the loads in R-phase will experience less voltage. Loads in Y-phase will experience almost same voltage. The neutral disconnect for an unbalanced system is dangerous to the loads. Because of the higher or lower voltages, the equipment is most likely to be damaged.
  • Here we observe that Neutral Floating condition does not impact on 3 Phase Load but It impacts  only 1 Phase Load only

How to Eliminate Neutral Floating:

  • There are Some Point needs to be consider to prevent of Neutral Floating.
a)    Use 4 Pole Breaker/ELCB/RCBO in Distribution Panel:
  • A floating neutral can be a serious problem. Suppose we have a breaker panel with 3 Pole Breaker for Three Phase and Bus bar for Neutral for 3 Phase inputs and a neutral (Here we have not used 4 Pole Breaker). The voltage between each Phase is 440 and the voltage between each Phase and the neutral is 230. We have single breakers feeding loads that require 230Volts. These 230Volt loads have one line fed by the breaker and a neutral.
  •  Now suppose the Neutral gets loose or oxidized or somehow disconnected in the panel or maybe even out where the power comes from. The 440Volt loads will be unaffected however the 230V loads can be in serious trouble. With this Floating neutral condition you will discover that one of the two lines will go from 230Volts up to 340 or 350 and the other line will go down to 110 or 120 volts. Half of your 230Volt equipment will go up in high due to overvoltage and the other half will not function due to a low voltage condition. So, be careful with floating neutrals.
  • Simply use ELCB, RCBO or 4 Pole Circuit Breaker as income in the 3ph supply system since if neutral opens it will trip the complete supply without damaging to the system.
b)   Using Voltage Stabilizer:
  • Whenever neutral fails in three phase system, the connected loads will get connected between phases owing to floating neutral. Hence depending on load resistance across these phases, the voltage keeps varying between 230V to 400V.A suitable servo stabilizer with wide input voltage range with high & low cutoff may help in protecting the equipments.
c)  Good workmanship & Maintenance :
  • Give higher Priority on Maintenance of  LV network  . Tight or apply adequate Torque for  tightening of Neutral conductor in LV system

Conclusion:

  • A Floating Neutral (Disconnected Neutral) fault condition is VERY UNSAFE because If Appliance is not working  and someone who does not know about the Neutral Floating could easily touch the Neutral wire to find out why appliances does not work when they are plugged into a circuit and get a bad shock. Single phase Appliances are design to work its normal Phase Voltage when they get Line Voltage Appliances may Damage .Disconnected Neutral fault is a very unsafe condition and should be corrected at the earliest possible by troubleshooting of the exact wires to check and then connect properly.