Calculate Min. Cross Section area of Earthing Conductor:
- Cross Section Area of Earthing Conductor As per IS 3043
Cross Section Area of Earthing Conductor (A) =(If x√t) / K
- Where t= Fault current Time (Second).
- K= Material Constant.
- Example:
- Calculate Cross Section Area of GI Earthing Conductor for System has 50KA Fault Current for 1 second. Corrosion will be 1.0 % Per Year and No of Year for Replacement is 20 Years.
- Cross Section Area of Earthing Conductor (A) =(If x√t) / K
- Here If=50000 Amp
- T= 1Second
- K=80 (Material Constant, For GI=80, copper K=205, Aluminium K=126).
- Cross Section Area of Earthing Conductor (A) =(50000×1)/80
- Cross Section Area of GI Earthing Conductor (A)=625 Sq.mm
- Allowance for Corrosion = 1.0 % Per Year & Number of Year before replacement say = 20 Years
- Total allowance = 20 x 1.0% = 20%
- Safety factor = 1.5
- Required Earthing Conductor size = Cross sectional area x Total allowance x Safety factor
- Required Earthing Conductor size = 1125 Sq.mm say 1200 Sq.mm
- Hence, Considered 1Nox12x100 mm GI Strip or 2Nox6 x 100 mm GI Strips
Thumb Rule for Calculate Number of Earthing Rod:
- The approximate earth resistance of the Rod/Pipe electrodes can be calculated by
Earth Resistance of the Rod/Pipe electrodes R= K x ρ/L
- Where ρ = Resistivity of earth in Ohm-Meter
- L= Length of the electrode in Meter.
- d= Diameter of the electrode in Meter.
- K=0.75 if 25< L/d < 100.
- K=1 if 100 < L/d < 600
- K=1.2 o/L if 600 < L/d < 300
Number of Electrode if find out by Equation of R(d) =(1.5/N) x R
- Where R(d) = Desired earth resistance
- R= Resistance of single electrode
- N= No. of electrodes installed in parallel at a distance of 3 to 4 Meter interval.
- Example:
- Calculate Earthing Pipe Resistance and Number of Electrode for getting Earthing Resistance of 1 Ω ,Soil Resistivity of ρ=40, Length=2.5 Meter, Diameter of Pipe= 38 mm.
- Here L/d = 2.5/0.038=65.78 so K=0.75
- The Earth Resistance of the Pipe electrodes R= K x ρ/L =0.75×65.78=12 Ω
- One electrode the earth resistance is 12 Ω.
- To get Earth resistance of 1 Ω the total Number of electrodes required =(1.5×12)/1 =18 No
Calculating Resistance & Number of Earthing Rod:
- Reference: As per EHV Transmission Line Reference Book page: 290 and Electrical Transmission & Distribution Reference Book Westinghouse Electric Corporation, Section-I Page: 570-590.
Earthing Resistance of Single Rods: R = ρx[ln (2L/a)-1]/(2×3.14xL)
Earthing Resistance of Parallel Rods: R = ρx[ln (2L/A]/ (2×3.14xL)
- Where L= length of rod in ground Meter,
- a= radius of rod Meter
- ρ = ground resistivity, ohm- Meter
- A= √(axS)
- S= Rod separation Meter
Factor affects on Ground resistance:
- The NEC code requires a minimum ground electrode length of 2.5 meters (8.0 feet) to be in contact with the soil. But, there are some factor that affect the ground resistance of a ground system:
- Length / Depth of the ground electrode: double the length, reduce ground resistance by up to 40%.
- Diameter of the ground electrode: double the diameter, lower ground resistance by only 10%.
- Number of ground electrodes: for increased effectiveness, space additional electrodes at least equal to the depth of the ground electrodes.
- Ground system design: single ground rod to ground plate.
The GI Earthing Conductor sizes for various Equipments:
No | Equipments | Earth Strip Size |
1
| HT switchgear, structures, cable trays & fence, rails, gate and steel column |
55 X 6 mm (GI)
|
2
| Lighting Arrestor |
25 X 3 mm (Copper)
|
3
| PLC Panel |
25 X 3 mm (Copper)
|
4
| DG & Transformer Neutral |
50X6 mm (Copper)
|
5
| Transformer Body |
50X6 mm (GI)
|
6
| Control & Relay Panel |
25 X 6 mm (GI)
|
7
| Lighting Panel & Local Panel |
25 X 6 mm (GI)
|
8
| Distribution Board |
25 X 6 mm (GI)
|
9
| Motor up to 5.5 kw |
4 mm2 (GI)
|
10
| Motor 5.5 kw to 55 kw |
25 X 6 mm (GI)
|
11
| Motor 22 kw to 55 kw |
40 X 6 mm (GI)
|
12
| Motor Above 55 kw |
55 X 6 mm (GI)
|
Selection of Earthing System:
Installations/ Isc Capacity
|
IR Value Required
|
Soil Type/ Resistivity
|
Earth System
|
House hold earthing/3kA | 8 ohm | Normal Soil/ up to 50 ohm-meter | Single Electrode |
Sandy Soil/ between 50 to 2000 ohm- meter | Single Electrode | ||
Rocky Soil/ More than 2000 ohm- meter | Multiple Electrodes | ||
Commercial premises,Office / 5kA | 2 ohm | Normal Soil/ up to 50 ohm-meter | Single Electrode |
Sandy Soil/ between 50 to 2000 ohm- meter | Multiple Electrodes | ||
Rocky Soil/ More than 2000 ohm- meter | Multiple Electrodes | ||
Transformers, substationearthing, LT line equipment/ 15kA | less than 1 ohm | Normal Soil/ up to 50 ohm-meter | Single Electrode |
Sandy Soil/ between 50 to 2000 ohm- meter | Multiple Electrodes | ||
Rocky Soil/ More than 2000 ohm- meter | Multiple Electrodes | ||
LA, High current Equipment./ 50kA | less than 1 ohm | Normal Soil/ up to 50 ohm-meter | Single Electrode |
Sandy Soil/ between 50 to 2000 ohm- meter | Multiple Electrodes | ||
Rocky Soil/ More than 2000 ohm- meter | Multiple Electrodes | ||
PRS, UTS, RTUs, Data processing centre etc./5KA | less than 0.5 ohm | Normal Soil/ up to 50 ohm-meter | Single Electrode |
Sandy Soil/ between 50 to 2000 ohm- meter | Multiple Electrodes | ||
Rocky Soil/ More than 2000 ohm- meter | Multiple Electrodes |
Size of Earthing Conductor:
- Ref IS 3043 &Handbook on BS 7671: The Lee Wiring Regulations by Trevor E. Marks.
Size of Earthing Conductor
| ||
Area of Phase Conductor S (mm2) | Area of Earthing conductor (mm2) When It is Same Material as Phase Conductor | Area of Earthing conductor (mm2) When It is Not Same Material as Phase Conductor |
S < 16 mm2 | S | SX(k1/k2) |
16 mm2<S< 35 mm2 | 16 mm2 | 16X(k1/k2) |
S > 35 mm2 | S/2 | SX(k1/2k2) |
K1 is value of Phase conductor,k2 is value of earthing conductor | ||
Value of K for GI=80, Alu=126,Cu=205 for 1 Sec |
Standard Earthing Strip/Plate/Pipe/wire Weight:
GI Earthing Strip:
Size (mm2) | Weight |
20 x 3 | 500 gm Per meter |
25 x 3 | 600 gm Per meter |
25 x 6 | 1/200 Kg Per meter |
32 x 6 | 1/600 Kg Per meter |
40 x 6 | 2 Kg Per meter |
50 x 6 | 2/400 Kg Per meter |
65 x 10 | 5/200 Kg Per meter |
75 x 12 | 7/200 Kg Per meter |
GI Earthing Plate:
Plate | Weight |
600 x 600 x 3 mm | 10 Kg App. |
600 x 600 x 4 mm | 12 Kg App. |
600 x 600 x 5 mm | 15 Kg App. |
600 x 600 x 6 mm | 18 Kg App. |
600 x 600 x 12 mm | 36 Kg App. |
1200 x 1200 x 6 mm | 70 Kg App. |
1200 x 1200 x 12 mm | 140 Kg App. |
GI Earthing Pipe:
Pipe | Weight |
3 meter Long BISE | 5 Kg App. |
3 meter r Long BISE | 9 Kg App. |
4.5 meter (15′ Long BISE) | 5 Kg App. |
4.5 meter (15′ Long BISE) | 9 Kg App. |
4.5 meter (15′ Long BISE) | 14 Kg App |
GI Earthing Wire:
Plate | Weight |
6 Swg | 5 meter in 1 Kg |
8 Swg | 9 meter in 1 Kg |