Standard: Northern Ireland Electricity (NIE), 6/025 ENA
Clearances of Electrical Line to Ground and Roads:
Description of Clearance |
0.4 KV
|
11 KV
|
33KV
|
110KV
|
220 KV
|
400KV
|
Line conductor to any point not over road |
5.2 Meter
|
6.1 Meter
|
6.4 Meter
|
6.4 Meter
|
7.0 Meter
|
7.0 Meter
|
Line conductor to road surface |
5.8 Meter
|
6.1 Meter
|
6.4 Meter
|
6.4 Meter
|
7.4 Meter
|
8.1 Meter
|
Line conductor to road surface of high load routes |
6.9 Meter
|
6.9 Meter
|
6.9 Meter
|
7.2 Meter
|
8.5 Meter
|
9.2 Meter
|
Bare live metalwork ( transformer terminals, jumper connections, etc) |
4.6 Meter
|
4.6 Meter
|
4.6 Meter
|
-
|
-
|
-
|
Clearances of Electrical Line to Other Objects:
Description of Clearance |
<11 KV
|
33 KV
|
110KV
|
220KV
|
400 KV
|
Line conductor or bare live metalwork to any object that is normally accessible (including permanently mounted ladders and access platforms) or to any surface of a building |
3.0 Meter
| 3.0 Meter | 3.4 Meter | 4.6 Meter | 5.3 Meter |
Line conductor or bare live metalwork to any object to which access is not required AND on which a person cannot stand or lean a ladder |
0.8 Meter
| 0.8 Meter | 1.2 Meter | 2.4 Meter | 3.1 Meter |
Line conductors to irrigates, slurry guns and high-pressure hoses |
30 Meter
| 30 Meter | 30 Meter | 30 Meter | 30 Meter |
Line conductors to playing fields |
8.5 Meter
| 8.5 Meter | 8.5 Meter | 8.5 Meter | 8.5 Meter |
Line conductors to Caravan Sites |
9.0 Meter
| 9.0 Meter | 9.0 Meter | 9.0 Meter | 9.0 Meter |
Horizontal clearances to wells |
15.0 Meter
| 15.0 Meter | 15.0 Meter | 15.0 Meter | 15.0 Meter |
Clearances of Electrical Line to Trees and Hedges:
Description of Clearance |
<11 KV
|
33 KV
|
110KV
|
220KV
|
400 KV
|
Line conductor or bare live metalwork to trees or hedges unable to support a ladder or being climbed. |
0.8 Meter
| 0.8 Meter | 1.2 Meter | 2.4 Meter | 3.1 Meter |
Line conductor or bare live metalwork to trees or hedges capable of supporting a ladder or being climbed. |
3.0 Meter
| 3.0 Meter | 3.4 Meter | 4.6 Meter | 5.3 Meter |
Line conductor or bare live metalwork to trees falling towards the overhead line with the line conductors hanging vertically. |
0.8 Meter
| 0.8 Meter | 1.2 Meter | 2.4 Meter | 3.1 Meter |
Line conductors to trees in Orchards |
3.0 Meter
| 3.0 Meter | 3.4 Meter | 4.6 Meter | 5.3 Meter |
Clearances of Electrical Line to Street Lighting:
Description of Clearance |
0.4 KV
|
11 KV
|
33KV
|
110KV
|
220 KV
|
400KV
|
Line conductor to Lantern on same pole |
1.0 Meter
|
-
|
-
|
-
|
-
|
-
|
Bare line conductor to lantern or column below. |
1.5 Meter
|
-
|
-
|
-
|
-
|
-
|
Insulated line conductor to column | 0.3 Meter |
-
|
-
|
-
|
-
|
-
|
Insulated line conductor to lantern | 1.0 Meter |
-
|
-
|
-
|
-
|
-
|
Column to nearest LV pole | 1.5 Meter |
-
|
-
|
-
|
-
|
-
|
Line conductor to street lighting column with | ||||||
(i) Column in normal upright position. | - | 1.7 Meter | 1.7 Meter | 2.3 Meter | 3.3 Meter | 4.0 Meter |
(ii) Column falling towards line with line conductor hanging vertically only | - | 1.7 Meter | 1.7 Meter | 2.3 Meter | 3.3 Meter | 4.0 Meter |
(iii)Column falling towards line | - | 0.4 Meter | 0.4 Meter | 0.8 Meter | 1.4 Meter | 1.9 Meter |
Clearances of Electrical Line to Waterways:
Description of Clearance |
0.4 KV
|
11 KV
|
33KV
|
110KV
|
220 KV
|
400KV
|
Navigable Waters:Lower bank to conductor or earth wire |
10.5 Meter
| 10.5 Meter | 10.5 Meter | 10.5 Meter | 10.5 Meter | 10.5 Meter |
Minor Watercourses :Lower bank to conductor or earth wire |
7.6 Meter
| 7.6 Meter | 7.6 Meter | 7.6 Meter | 7.6 Meter | 7.6 Meter |
Clearances to Railways:
Description of Clearance |
0.4 KV
|
11 KV
|
33KV
|
110KV
|
220 KV
|
400KV
|
Line conductor to ground level |
6.1 Meter
| 6.1 Meter | 6.1 Meter |
6.7 Meter
|
7.0 Meter
|
7.6 Meter
|
Line conductor to ground level on or across vehicle parks | 7.6 Meter | 8.5 Meter | 8.5 Meter | 9.1 Meter | 9.4 Meter | 10.1 Meter |
Line conductor to ground level at roads and yards, where road mobile cranes are likely to be employed | 10.7 Meter |
10.7 Meter
|
10.7 Meter
|
11.2 Meter
|
11.5 Meter
|
12.2 Meter
|
Line conductor to Rail level | 7.3 Meter | 7.3 Meter | 7.3 Meter | 8.0 Meter | 8.2 Meter | 8.8 Meter |
Line conductor to the level of buildings, gantries or other structures (including those carrying traction wires) on which a man may be | 3.0 Meter | 3.0 Meter | 3.0 Meter | 3.7 Meter | 4.6 Meter | 6.1 Meter |
Line conductor to poles and other projections. | 2.4 Meter | 2.7 Meter | 2.7 Meter | 3.0 Meter | 3.7 Meter | 5.5 Meter |
Line conductor to any other wire other than traction wires. | 1.8 Meter | 1.8 Meter | 1.8 Meter | 2.4 Meter | 3.0 Meter | 3.7 Meter |
Clearances of Electrical Line to Fuel Tanks:
Description of Clearance
|
0.4 KV
|
11 KV
|
33KV
|
110KV
|
220 KV
|
400KV
|
Horizontal clearance from line conductors to petrol tanks and vents |
15 Meter
|
15 Meter
|
15 Meter
|
15 Meter
|
15 Meter
|
15 Meter
|
Horizontal clearance from line conductors to liquid gas tanks | ||||||
(1) 459 to 2273 litre capacity |
3.0 Meter
|
3.0 Meter
|
3.0 Meter
|
3.4 Meter
|
4.6 Meter
|
5.3 Meter
|
(2) 2274 to 9092 litre capacity |
7.6 Meter
|
7.6 Meter
|
7.6 Meter
|
7.6 Meter
|
7.6 Meter
|
7.6 Meter
|
(3) More than 9093 litre. |
15 Meter
|
15 Meter
|
15 Meter
|
15 Meter
|
15 Meter
|
15 Meter
|
Vertical clearance from line conductors to fuel oil tanks |
Please refer Clearances to Objects
|
Clearances of Electrical Lines to other Electrical Lines:
Description of Clearance
|
0.4 KV
|
11 KV
|
33KV
|
110KV
|
220 KV
|
400KV
|
Lowest line conductor or earth wire of upper line to highest line conductor of lower line. |
1.0 Meter
|
1.8 Meter
|
2.0 Meter
|
2.5 Meter
|
3.7 Meter
|
4.4 Meter
|
Lowest line conductor or earth wire of upper line to earth wire of lower line where erected. |
0.7 Meter
|
1.4 Meter
|
1.6 Meter
|
2.5 Meter
|
3.7 Meter
|
4.4 Meter
|
Lowest line conductor or earth wire of upper line to any point on a support of the lower line on which a person may stand. |
2.7 Meter
|
2.8 Meter
|
3.0 Meter
|
3.4 Meter
|
4.6 Meter
|
5.3 Meter
|
Support of upper line and any conductor of lower line. |
7.5 Meter
|
7.5 Meter
|
7.5 Meter
|
15 Meter
|
15 Meter
|
15 Meter
|
Vertical Passing Clearance (sites where vehicles will pass below the lines):
Description of Clearance |
<33 KV
|
110KV
|
220KV
|
400 KV
|
Passing clearance: fixed height loads
| 0.8 Meter | 1.4 Meter | 2.4 Meter | 3.1 Meter |
Passing Clearance: variable height loads.
| 2.3 Meter | 3.2 Meter | 4.1 Meter | 5.0 Meter |
Horizontal Clearance (sites where there will be no work or passage of plant under lines):
Description of Clearance |
<33 KV
|
110KV
|
220KV
|
400 KV
|
Minimum horizontal distances to safety barriers
|
6.0 Meter
| 9.0 Meter | 12.0 Meter | 14.0 Meter |
Distance between Conductors of Same/Different Circuit (On Same Support):
Higher Voltage of either Circuit |
Lower Voltage of either Circuit
|
Distance between Circuits
|
< 33 KV
|
< 1 KV
|
1.0 Meter
|
< 33 KV
|
> 1 KV
|
1.2 Meter
|
33 KV to 110 KV
|
< 1 KV
|
1.5Meter
|
33 KV to 110 KV
|
> 1 KV
|
2.0 Meter
|
Above 110 KV
|
All
|
2.5 Meter
|
Vertical Distance between Conductors of different Circuit (On Different Support):
Higher Voltage of either Circuit |
Distance between Circuits
|
< 1 KV
|
0.6 Meter
|
1 KV to 33 KV
|
1.2 Meter
|
33 KV to 66 KV
|
1.8 Meter
|
110 KV
|
2.4 Meter
|
220 KV
|
2.8 Meter
|
Distance between Conductors (Taken down from Pole to other Support, on Transformer):
Voltage |
Distance between Circuits
|
11 KV & LV Line
|
0.60 Meter
|
22 KV & LV Line
|
0.75 Meter
|
33 KV & LV Line
|
0.90 Meter
|
Horizontal Distance of Telecommunication Line & Overhead Line:
Description of Clearance |
Distance
|
Telecommunication Line(Not insulated) to HV Line |
Min 1.6 Meter
|
Telecommunication Line (Bare) to LV (Bare) Line | Min 1.2 Meter |
Telecommunication Line (Covered) to LV (Bare) Line | Min 0.6 Meter |
Telecommunication Line (Bare) to Stay (Bare) Wire | Min 0.3 Meter |
Passage Way for Metal clad Switchgear:
Description of Clearance |
Distance
|
Clean &unobstructed Passages at the front of any Low/High Voltage Switchgear. |
1.0 Meter wide & 2.5 Meter high
|
Clean &unobstructed Passages at side or under any earthed enclosure containing Bare Conductor | 0.8 Meter wide & 2.2 Meter high |
Safe approach distance for Person from Exposed Live Parts:
Circuit Voltage |
Distance
|
< 1 KV |
0.5 Meter
|
11 KV |
1.5 Meter
|
22 KV |
2.0 Meter
|
33 KV |
2.5 Meter
|
66 KV |
3.0 Meter
|
110 KV |
4.0 Meter
|
>220 KV |
6.0 Meter
|